MaxCell product descriptions do not directly correlate to the size of conduits. 4” 3-Cell or 3” 3-Cell are not meant specifically for 4” or 3” conduits. The description only applies to the width of the product when pressed flat. General guidelines for deciding which MaxCell to use in various applications.

  4" 3-CELL

4 Inch 3-CELLThis product was designed for use in 4" or larger ducts. Multiple combinations of large and medium cable sizes are applicable. Since larger cable applications are anticipated, the number of cables and packs that can be placed is reduced; therefore, a smaller number of cables is available.

MIN CONDUIT ID
MAX # OF PACKS
MAX # OF CABLES
MAX CABLE DIAMETER PER CELL
REC. PULL LENGTH*
MAX PULL LENGTH*
4" 2 6 1.5" 1,250' 2,000'
5" 3 9 1.5" 1,250' 2,000'
6" 4 12 1.5" 1,250' 2,000'

  3" 3-CELL

3 Inch 3-CELLThis product was designed for use in 3" or larger ducts. Multiple combinations of large, medium and smaller cable sizes are applicable and anticipated.

MIN CONDUIT ID
MAX # OF PACKS
MAX # OF CABLES
MAX CABLE DIAMETER PER CELL
REC. PULL LENGTH*
MAX PULL LENGTH*
3" 2 6 1.05" 1,250' 2,000'
4" 3 9 1.05" 1,250' 2,000'
5" 4 12 1.05" 1,250' 2,000'
6" 5 15 1.05" 1,250' 2,000'

  2" 3-CELL

2 Inch 3-CELLThis product was designed for use in 2" ducts where three cables are being placed.

MIN CONDUIT ID
MAX # OF PACKS
MAX # OF CABLES
MAX CABLE DIAMETER PER CELL
REC. PULL LENGTH*
MAX PULL LENGTH*
2" 1 3 .85" 800' 1,500'

  2" 2-CELL

2 Inch 2-CELLThis product was designed for use in 2" ducts where two cables are being placed.

MIN CONDUIT ID
MAX # OF PACKS
MAX # OF CABLES
MAX CABLE DIAMETER PER CELL
REC. PULL LENGTH*
MAX PULL LENGTH*
2" 1 2 .85" 800' 1,500'

  2" 1-CELL

2 Inch 1-CELLThis product was designed for use in 1.5" and 2" ducts. It is designed to deploy an additional cable in a confined small conduit or innerduct.

MIN CONDUIT ID
MAX # OF PACKS
MAX # OF CABLES
MAX CABLE DIAMETER PER CELL
REC. PULL LENGTH*
MAX PULL LENGTH*
1.5" + 1 1 .85" 800' 1,500'

  MaxCell Edge

MaxCell EdgeFor use in 1.25" to 2" Conduits in 1, 2 and 3-Cell Configurations.

MIN CONDUIT ID
SUGGESTED PRODUCT
MAX # OF PACKS
MAX # OF CABLES
MAX CABLE DIAMETER PER CELL
REC. PULL LENGTH*
MAX PULL LENGTH*
1.25" MXE3212-2 Cell 1 2 .45" 800' 1,500'
1.50" MXE3614-2 Cell 1 2 .55" 800' 1,500'
1.75" MXE4418-3 Cell 1 3 .70" 800' 1,500'
2.00" MXE5222-3 Cell 1 3 .85" 800' 1,500'

* Use of OFNR cable may result in reduced pulling lengths. Designers should make every effort to conform to industry standards with regard to distances between any two pull points (generally 600 to 1,000 feet), number of bends (maximum of two 90 degree bends or a total of 180 degrees) between any two pull points, and proofing of conduit pathway using appropriately sized mandrels (normally ¼ to ½ inch less than the inside diameter of the conduit).